9752 Installation Guide 3. Installation
11976870 Page 35
Line Monitoring for a Dual-Path Communicator
If a standalone dual-path (landline and mobile) communication device, such
as a RedCARE STU, is connected to the plug-by connector, you need to do
the following to obtain correct line fault reporting:
1. Wire a control unit output programmed as type "ATS Test" to the ATS Test
input of the communicator. Invert the sense of the output at the control unit
if a "positive applied" input sense is used at the communicator.
2. Wire the Line Fault output of the communicator to the Line Fault input of
the plug-by connector. The communicator must provide +12Vdc to indicate
a line fault (e.g. if the Line Fault output at the communicator uses a relay,
connect the common terminal of the relay to +12Vdc and the normally-
open terminal to the Line Fault input of the plug-by connector).
The control unit will generate an "ATE L.F. Single" alert if only one of the
networks is not available, or "ATE L.F. All" if both networks are not available.
Note: “ATS Test” output type is only available with version 4.02.06 software
and higher. This output type is required in order to conform to Form 175
Dual Signalling Line Fault enunciation.
Fitting a Battery
Fit a rechargeable battery into the back of the case. There is space in the
case for a 17Ah battery; to use this, order with part number MS100.
Cooper Security Ltd recommend that you fit at least a 7Ah battery.
Initial Start Up
Before applying power to the control unit, ensure that:
All keypads and expanders have been addressed and connected.
All external and internal sounders are connected.
All wired zone circuits are connected.
Then:
1. Connect the battery to the control unit PCB.
2. Briefly short the Kick Start pins together (see Figure 3).
The internal sounder may sound. Ignore any display at this stage.
3. Key in the factory default User access code: 1234.
The internal sounder stops. Ignore any display or lamps.
4. Fit the case lid before applying mains power (this covers the live wiring
and closes the tamper switch).
5. Apply mains power.
6. Key in the factory default Engineer Code: 7890.