3. Installation 9651
Page 12 11772232
Cabling for Keypads
Cooper Security recommends that you use 8-core 7/0.2 or 16/0.2 alarm cable
for wiring keypads. You can connect the keypads in either a star or bus
configuration. If you intend to use long cable runs, Cooper Security
recommends that you use star wiring with no more than 200m of cable per
branch.
The maximum length of any one run from the control unit to the most remote
keypad depends on the number of items connected to the cable. You can
double the maximum length for 7/0.2 cable by using two cores each for the 0V
and 12V terminals or by using 16/0.2 cable. The table below shows the
maximum recommended cable lengths in metres for 7/0.2 cable, assuming
that you connect all keypads at the end of a single cable run. You may be
able to improve on these figures by spreading keypads along the cable length.
8-core 7/0.2 cable
Number of kpds 1 core 2 cores on 0V and 12V
One 200
Two 100 200
Three 65 130
Four 50 100
It is possible to extend the keypad cable run by using additional power
supplies, but only up to the recommended maximum of 200m.
When carrying out the cabling, there are two important points to remember:
1. Do not connect anything other than keypads to the bus. The keypad bus
power supply is limited to a maximum of 400mA.
2. Check between 0V and 12V on the keypad bus at the point furthest from
the control unit: the voltage must be at least 12.0VDC when all the keypad
backlights are on.