Programming - Programming Commands 9651
Page 64 11772232
Example 1
Panel output 3 is to be programmed as type 12 (Pulse Set 1). It will be used to
operate a locking mechanism when the whole system is set. The locking
mechanism requires a 6-second pulse. The table below shows how to
program the system to generate the required pulse.
Command Value Description
83 12 Sets panel output 3 to type Pulse Set 1.
170 Set 1 = 06 Sets the duration of Pulse Set 1 to 6 seconds.
171 Set 1 = a Allocates Pulse Set 1 to Level A .
182: Set Final Exit Settling Time
This command defines a time delay to allow detectors to settle before the
system sets. This may be needed if detectors are being set off by air
movements caused by the final door being closed. During this period, the
sounders stop and the system sets but the control unit ignores any alarms
generated by the detectors.
Enter two digits to specify a time in seconds, from 07 to 12 (default is 07).
183: Set Display Line 2
This command sets the message that the control unit shows on the second
line of keypad displays in user mode. Key in a message of up to 16 characters
("Zone Names" on page 35 explains how to enter characters). The default text
identifies the control unit model used in the system.
184: Pulsed External Sounder for Fire
This command instructs the control unit to send a pulse to bell-type panel
outputs (configured with Commands 81–83, option 00) to signal a Fire alarm.
This can be used to drive the external sounders, giving a different alarm
sound from the normal continuous bell tone.
Option
0 Off (default). Use normal two-tone Fire alarm.
1 On. Send a pulse to bell-type outputs in the system.
185: Keyswitch Auto Reset
This command instructs the control unit to reset automatically if the user uses
the keyswitch to set the system on leaving.
Option
0 Off (default). User must reset manually.
1 On. System resets automatically when the user sets it with a
keyswitch (KM or KF).