Cooper Security Homelink 75 Guide de l'utilisateur Page 81

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 84
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 80
7510r
Page 77
Appendix A: DD243 Compliance
Applicability
Please study this section if the following applies:
1. You are installing an alarm system in the United
Kingdom.
2. The system has remote signalling and requires the
local Police Authority to issue a URN (Unique Reference
Number).
3. You have chosen to use "Sequential Alarm
Confirmation" to comply with DD243: 2004.
Note: The installed system will only fully comply with the
requirements of DD243: 2004 if it has been designed
in accordance with this section.
Setting (Clause 6.3)
To comply with the subsections of DD243:2004
paragraph 6.3:
6.3a) Connect the final exit door shunt lock to a wired
zone programmed as a keyswitch zone type.
Program the partition belonging to that zone as
“instant set”.
6.3b) You cannot use an exit terminate button with
Homelink 75.
6.3c) Program the exit mode as “final door set”.
6.3d) Program a telecommand to set the required
partitions. Program each partition as “instant set”.
Vue de la page 80
1 2 ... 76 77 78 79 80 81 82 83 84

Commentaires sur ces manuels

Pas de commentaire