48
049 – Monitored O/P On
If the output is latched, the output activates when a zone that has the Monitored attribute
(page 30) is activated and deactivates when the zone deactivates. If the output is pulsed, it
activates when a zone that has the Monitored attribute activates and remains active for
the pulse duration.
050 – Alarm Abort
Activates after an alarm has been aborted by the user; deactivates when the Abort Period
timer (page 63) has expired, or when the alarm is reset (whichever occurs first).
051 – Rem Call Enabled
Not used.
052 – Relearn Required
Activates when the system needs an engineer to confirm the devices attached to the
panel's network ports (e.g. after a new device is attached); deactivates when the relearn
has been performed.
053 – Always On
Active at all times.
054 – Always Off
This output never activates.
055 – Battery Test On
Activates during a battery test. The test starts when an engineer logs out, and lasts for
approximately 10 seconds. If required, the output can be used by the battery test input of
a monitored power supply.
056 – Battery Fault
Activates when the backup battery in the panel is not charging or has a low voltage.
057 – PSU - Battery
Activates while a PSU Battery zone (page 26) is active.
058 – PSU - Fuse
Activates while a PSU Fuse zone (page 26) is active.
059 – PSU - Power
Activates while a PSU Power zone (page 26) is active.
060 – General Fault
Activates when there is a general fault. A general fault occurs if one of the following
occurs.
Panel mains fail Panel Battery Fault
Remote PSU mains fail Remote PSU Battery Fault
Mains fail panel/MSPSU Battery Fail panel/remote PSU
PSU Battery zone (page 26) active Remote PSU power out fail
PSU Fuse zone (page 26) active Panel Aux fuse fail