Engineer Menu 1-5 Engineering Manual
62
Option 1-5-2: Setting Up System Timers
Timers 2
System Timers
Confirmation 01
030 Minutes
e.g.
[
Eng 1 Menu 5
Timers
Sys Bell Dly 02
000 Minutes
Sys Bell Dly 02
> 000 Minutes
Sys Bell Dly 02
> 005 Minutes
Timers 1
Ward Timers
[
|
[
[
|
|
e.g.
X
To select the timer typ e:
Press or
to scroll, or
Press the hot key (e.g. 05)
Press to save changes and view
next timer
[
1. SELECT "SYSTE
TIMERS" OPTION
2. SELECT
TIMER TYPE
3. EDIT TIMERVALUE
five times
To select timer valu e:
Press or
to scroll, or
Enter the value (e.g. 010)
The System Timers option enables you to set up time periods and counters that relate to the
whole system, such as entry and exit delays, bell duration and the number of "knocks" required
for alarm activation.
System Timer Types
In step 2, choose the timer type (for defaults see page 133 ):
01 – Confirmation
This timer is relevant only if the Confirmation On option is selected (page 89). A confirmed
alarm occurs only if the two zones trigger within the time period specified by this timer. If
the second zone is not triggered within this time period, the sounders and strobe are
cancelled, overriding the Bell Duration (page 61) or Sys Bell Dur (page 63) time, and the
system re-arms (isolating any zones that are still triggered).
02 – Sys Bell Dly
When a full alarm is triggered, activation of the external bell and strobe outputs can be
delayed by the value of this timer. This timer is used only if the system is full set and the
Global Bell Time configuration option is selected (see page 86). Otherwise, the ward Bell
Delay timer (page 61) is used.