4. Programming
Page 66 496964
Value Attribute Valid for Description
X2
Soak Test
(S)
Normal Alarm
(NA)
Entry Route
(ER)
24-hour (24)
Shock
Analyser
(SA)
Use this zone attribute if you want to
place on long-term test a detector that
you suspect is giving false alarms.
Zones with this attribute are disabled
for 14 days after you return the control
unit to user mode. If the zone is
opened while the system is set, the
Service LED glows and the control unit
logs the event as a "Soak Test Fail Zn"
(n = zone number) without sounding
any bells or starting signalling. The
Service LED stays on until the
Engineer resets the system. The
control unit returns the zone to normal
use after 14 days, even if the system is
set at the time.
X3
Double
Knock (D)
Normal Alarm
(NA)
Entry Route
(ER)
Zones with this attribute will cause an
alarm condition only if one or more
sensors generate two alarm events
within a five-minute period, or if one
zone remains open for more than 10
seconds. Programming a zone as
"Double Knock" is a way of reducing
false alarms caused by environmental
changes but is not normally
recommended.
Do not apply "Double Knock" to radio
zones with a PIR detector. The radio
PIR uses a lockout timer and the
detector will not send a second
activation within the Double Knock
period.
X4
Omit
Allowed (O)
All When applied to a zone, this attribute
allows the user to omit the zone when
setting the alarm. This is useful for
ignoring non-critical faults, particularly
in busy areas like kitchens. Do not
allow the user to omit PA zones.
Do not apply this attribute to an FE
zone if there is no ER zone present.