4. Programming
Page 68 496964
Zones and Partitions
In a partitioned system, you can assign some zone types to two or more
partitions, and some zone types to one partition only.
One partition only More than one partition
Panic Alarm (PA)
Fire (FR)
24-hour (24)
Technical (TC)
Smoke Detector (SD)
Keyswitch – Momentary (KM)
Keyswitch – Fixed (KF)
Normal Alarm (NA)
Final Exit (FE)
Entry Route (ER)
Shock Analyser (SA)
Keybox (KB)
Anti-Mask (AM)
Forbikobler (FB)
Use those zone types that can be assigned to more than one partition to
create a common area (see page 121).
20: Change Engineer Code
Note: The 9752 and 9851 control units support six-digit access codes as well
as the standard four-digit codes. Command 56 sets the code length.
To change the Engineer Code:
1. Make sure you are in programming mode.
2. Key in 20 and press Y.
The display shows:
20:Code
3. Key in a new Engineer Code.
The display shows:
20:Code xxxx
4. Press Y.
If Guard Code is enabled (Command 181), the display shows:
20:Guard
3. Key in a new Guard Code.
The display shows:
20:Guard xxxx
4. Press Y.