4. Programming
496792 41
To change: Key-in: Notes Default
Answer On One Ring 113 0 One ring off Y
Downloading option 1 One ring on
Access Mode 114 0 Callback off (Attended) Y
1 Callback on
2 Callback any (Unattended)
Communicator Tel No 1 115 Maximum 31 digits
Communicator Tel No 2 116 Maximum 31 digits
Account No 1 117 Maximum 6 digits
Downloader Tel No 1 118 Maximum 31 digits
Downloader Tel No 2 119 Maximum 31 digits
Enable Downldr Tel No 3 120 0 Downloader Tel No 3 Off
1 Downloader Tel No 3 enabled.
Fast Format Channels 121 a b
For built in Communicator a is the channel number 1 to 8
b is one of the following:
00 Not Used 11 AC Fail
01 Fire (default Ch 1) 12 Tamper Alarm
02 PA (default Ch 2) 13 Open
03 Burglar (default Ch 3) 14 Close
04 Open/Close (default Ch 4) 15 Zone Omitted (default Ch 5)
05 Alarm Abort (default Ch 6) 16 Medical
06 Technical Alarm (default Ch 8) 17 Key-Box
07 Alarm Confirmation (dlt Ch 7) 18 Anti-Mask
08 RF Low Battery 19 Smoke Detector
09 RF Supervision Loss
10 Jamming
Comms Acknowledge 122 0 Off Y
1On
Note: Options are only available if Command 126 is set to option 1 (Ireland).
Restoral Reporting 123 0 Restore off Y
1 Restore on
Reverse Open/Closed 124 0 Disabled
1 Reverse codes
No Close if CCT Omitted 125 0 Disabled
(9752 only) 1 No close sent if more than one cct omitted.
Language 126 nn
nn = Language, one of:
0 = English(Y) 3 = Portuguese 6 = German 9 = Danish
1 = Italian 4 = Dutch 7 = Norwegian
2 = Spanish 5 = French 8 = Swedish
Vue de la page 46
1 2 ... 42 43 44 45 46 47 48 49 50 51 52 ... 95 96

Commentaires sur ces manuels