2. Programming Commands
497096, issue 3 Page 43
105: Static Test Call
With static testing, the control unit makes test calls at fixed times or intervals;
alternatively, you can use Command 108 (see page 44) to set up a dynamic
test call for 24 hours after the last communication.
Note: Cooper Security recommends that you choose either Static Test Call (105) or
Dynamic Test Call (108), but not both at the same time.
To disable static test calls, key in "00".
To make static test calls at a regular time, you have two options:
Ann To make a static test call at a set time every day, press A and then key in
a number between 01 and 24 to select the time for the call. For example,
key in "18" to program the control unit to make a call at 6.00pm every
day.
Bnn To make a static test call on a set day of every month, press B and then
key in a number between 01 and 28 to select the day for the call. For
example, key in "22" to program the control unit to make a call on the
22
nd
day of every month. The call will be made at 1.00am.
To make static test call at regular intervals, you have two options:
Cnn To make a static test call every nn hours, press C and then key in a
number between 01 and 24 to select the interval in hours. For example,
key in "12" to program the control unit to make a call every 12 hours.
Dnn To make a static test call every nn days, press D and then key in a
number between 01 and 28 to select the interval in days. For example,
key in "07" to program the control unit to make a call every 7 days.
The control unit adjusts call timing by a random interval (up to 16 minutes) to
ensure that the Alarm Receiving Centre (ARC) is not overwhelmed by a flood
of test calls from systems that have all been set with the static test options.
Note: Compliance with PD 6662 / prEN 50131-1: 2004 Grades 1 and 2 (see page 85)
requires that a test call is made within 25 hours of the last communication. Grade 3
requires the call to be within five hours. If you use static test calls, choose an
appropriate interval.