2. Programming Commands
497096, issue 3 Page 59
159: Invert Plug-by Outputs
By default, plug-by outputs have a positive voltage when inactive and this is
removed when the output is active. This command inverts that logic so that a
positive voltage is applied when the output is active.
Option
0 +ve removed to trigger (default): the output is positive when inactive
and goes to zero when active.
1 +ve applied to trigger: the output floats when inactive and goes
positive when active.
160: Confirmed Alarm Timer
Note: Set Alarm Confirmation (Command 89) to 1 to access this command.
This command controls a timer, which starts when an alarm is triggered for
the first time. If a second alarm is triggered before the timer expires, the
control unit transmits a confirmed alarm to the Alarm Receiving Centre (ARC).
You can set the timer to any value between 001 and 999 minutes (default 30).
Note: Compliance with DD 243: 2004 (see page 83) requires that Command 160 is set to
a value of 30 to 60 minutes.
161: Internal Sounder on Confirmed or Unconfirmed Alarm
Note: Set Alarm Confirmation (Command 89) to 1 or 2 to access this command.
This command selects whether the control unit will operate the internal
sounder for a confirmed alarm or for an unconfirmed alarm. In a partitioned
system, the internal sounder is available only for Partition A; other partitions
use keypad sounders only.
Option
0 Control unit operates the internal sounder for a confirmed or
unconfirmed alarm (default).
1 Control unit operates the internal sounder only for a confirmed alarm.
Note: Compliance with DD 243: 2004 (see page 83) requires that Command 161 is set to 0.