2. Programming Commands
497096, issue 3 Page 63
180: Print Log (9853 only)
This command instructs the control unit to print the event log through the
serial port on the main PCB. Selecting option 1 causes events to be printed as
they occur until the mode is cancelled by selecting option 0. To print the log
during testing, use Command 90, options 0 and 7, as described on page 70.
Option
0 Off (default). Do not print the event log.
1 On. Print the event log.
Note: The log is protected and cannot be erased by the Installer or a user.
181: Enable Guard Code
This command selects whether the control unit supports a Guard Code (set
with Engineer Code using Command 20). A user with Guard access can unset
the system but only after an alarm, which will be recorded in the event log.
Option
0 Off (default). No Guard Code.
1 On. Guard Code.
182: Set Final Exit Settling Time
This command defines a time delay to allow detectors to settle before the
system sets. This may be needed if detectors are being set off by air
movements caused by the final door being closed. During this period, the
sounders stop and the system sets but the control unit ignores any alarms
generated by the detectors.
Enter two digits to specify a time in seconds, from 07 to 12 (default is 07).
183: Set Display Line 2
This command sets the message that the control unit shows on the second
line of keypad displays in user mode. Key in a message of up to 16 characters
("Zone Names" on page 7 explains how to enter characters). The default text
identifies the control unit model used in the system.
184: Pulsed External Sounder for Fire
This command instructs the control unit to send a pulse to bell-type panel
outputs (configured with Commands 81–84, option 00) to signal a Fire alarm.
This can be used to drive the external sounders, giving a different alarm
sound from the normal continuous bell tone.
Option
0 Off (default). Use normal two-tone Fire alarm.
1 On. Send a pulse to bell-type outputs in the system.