2. Programming Commands
497096, issue 3 Page 61
164: User/Engineer Reset after Confirmed Alarm
Note: Set Alarm Confirmation (Command 89) to 1 or 2 and Enable Engineer Reset
(Command 33) to access this command.
Use this command to select who can reset the system after a confirmed
alarm.
Option
0 User/Engineer (default). The user can reset the system after a first
alarm but an engineer is required to reset after a confirmed alarm.
1 User/User. The user can reset the system after both types of alarm.
2 Engineer/Engineer. An engineer is required to reset the system after
both types of alarm.
Note: Compliance with DD 243: 2004 (see page 83) requires that Command 164 is set to
(a) option 0 or 2 for sections 6.4.4 and 6.4.5 or (b) option 1 for sections 6.4.2, 6.4.3
and 6.4.6. This means that a user cannot reset the system after a confirmed alarm
unless the system is unset using a keyswitch, lockswitch or by calling an Alarm
Receiving Centre (ARC).
165 to 169: Not used
These commands are not used.
170 to 175: Pulse Output Programming
You can program the panel outputs to generate a pulse of a defined length
when triggered by a set or unset event. Pulses of different lengths can be set
for each level or partition. Commands 170 to 175 enable you to configure
these pulse outputs. Press y to move between the outputs within each
command.
Command Value Default Description
170 00* to 12 01 Specifies the length in seconds of the pulse to
be generated on setting.
* A value of 00 latches the output.
171 A/B/C/D abcd Assigns each pulse set output to one or more
levels or partitions.
172 00* to 12 01 Specifies the length in seconds of the pulse to
be generated on unsetting.
* A value of 00 latches the output.
173 A/B/C/D abcd Assigns each pulse unset output to one or more
levels or partitions.
174 0 (Off) or 1
(On)
On Specifies whether each pulse unset output is
activated for a Fire alarm.
175 0 (Off) or 1
(On)
On Specifies whether each pulse unset output is
activated for a PA.