i-on160 Installer Menu Options
Page 63
6.4.5).
Entry Keypad Lock
This option determines whether the user can unset the system by entering an
access code after opening the entry door.
Off The user can enter an access code at the keypad after the entry
door opens (used for DD243:2004 clause 6.4.4).
On The user must unset the system by some means other than the
keypad, for example prox tag, remote control or key-switch (used
for DD243:2004 clause 6.4.5).
Note: This option functions when confirmation is ON and communications is
enabled. If communications is disabled this option has no effect.
Sounder on
Unconfirm When the system is set the control unit activates the internal
sounders when an unconfirmed alarm occurs.
Confirm When the system is set the control unit does not activate the
internal sounders until a confirmed alarm occurs.
Note: The control unit will not allow you to select “Sounder on - Confirm” at
the same time as “Siren on - Unconfirm”.
Siren on
Unconfirm the control unit operates the siren for all alarms (and overrides
any Siren Delay).
Confirm When the system is set the control unit does not activate the
siren(s) until a confirmed alarm occurs.
Note: The control unit will not allow you to select “Siren on - Unconfirm” at the
same time as “Sounder on - Confirm”.
Siren Delay and DD243
The Sounder On and Siren On options are both affected by the Siren Time and
Siren Delay, as follows:
Sounder On Unconfirm/Siren On Unconfirm
Unconfirmed alarm: internal sounders and sirens start immediately and run for
the programmed siren time (see page 69).
Confirmed alarm: the control unit restarts the sirens and internal sounders,
which run for the full programmed siren time (even if that had expired earlier).
Sounder On Unconfirm/Siren On Confirm
Unconfirmed alarm: the internal sounders start immediately and run for the
programmed siren time.
Confirmed alarm: the control unit waits for any programmed siren delay (see
page 69) and then starts both the internal sounders and the external sirens.
These both run for the programmed siren time.
Sounder On Confirmed/Siren On Confirmed
Unconfirmed alarm: No sounders or sirens.